G-93-05-13-11D - 5/13/1993ORDINANCE NO. 4 - 93- 05- 43- - l / D
AN ORDINANCE AMENDING THE CODE OF ORDINANCES (1990
EDITION), CITY OF ROUND ROCK, TEXAS, CHAPTER 3, SECTION
3.901(2) TO ADOPT THE 1993 EDITION OF THE NATIONAL
ELECTRICAL CODE; AMENDING SECTION 3.901(7) TO AMEND
REFERENCES TO THE 1990 EDITION TO THE 1993 EDITION;
AMENDING SECTION 3.905(1) TO DELETE REFERENCE TO
SURETY BOND; REPEALING SECTION 3.906(8) TO ELIMINATE
THE REQUIREMENT FOR A BOND; AMENDING SECTION 3.906(9)
TO DELETE THE REFERENCE TO A BOND; REPEALING SECTION
3.906(12); PROVIDING FOR A SAVINGS CLAUSE AND REPEALING
CONFLICTING ORDINANCES OR RESOLUTIONS.
BE IT ORDAINED BY THE COUNCIL OF THE CITY OF ROUND ROCK,
TEXAS, THAT:
I.
The Chapter 3, Section 3.901(2), Code of Ordinances (1990
Edition), City of Round Rock is hereby amended to read as follows:
(2) National Electrical Code, NFPA 70
The National Electrical Code, NFPA
(hereinafter referred to as "NEC") , as
hereby adopted as part of this Code to
if it were copied verbatim herein and
except as it may be in conflict with
this Code.
70 1993 Edition
amended herein, is
the same effect as
shall be in effect
the provisions of
II.
The Chapter 3, Section 3.901(7), Code of Ordinances (1990
Edition), City of Round Rock is hereby amended to read as follows:
(7)
OR05133D
Amendments to the National Electrical Code, 1993 Edition
(a) Article 210-8(a), National Electrical Code, 1993
Edition, is hereby amended by adding subparagraph
(7) which shall read as follows:
(7)
All receptacles protected by one (1) or more
ground -fault circuit interupter devices shall
be identified.
(b) Article 220, National Electrical Code, 1993
Edition, is hereby amended by deleting Section 22
and substituting the following:
220-22. Neutral Conductor
Neutral conductors shall be of the same ampacity as
the largest ungrounded conductor.
(c) Article 230, National Electrical Code, 1993
Edition, is hereby amended by deleting Section 2
and substituting the following:
230-2. Services
(a) Single Occupancy;
If a building is
then a single
disconnect shall
building.
(b)
Less Than 1000 Amps
to house only one occupant
current limiting service
be installed outside the
Single Occupancy; 1000 Amps or More
If a building is to house only one occupant,
has a total service entrance capacity of 1000
amps or more, and arrangements have been made
with the power supplier for the installation
of a three-phase padmounted transformer, then
multiple service current limiting
disconnecting means may be installed, with
special permission from the Electrical Board,
at one location outside the building, up to a
maximum number of six (6). Furthermore, the
service disconnecting means may be installed
inside the building on the ground floor. In
this case, the disconnects shall be located no
more than twenty-four (24) inches from the
point of the Service Conductors, direct access
shall be provided within ten (10) feet of the
disconnects from outside the building, and
doors leading to the disconnects shall be
secured by only a padlock and hasp. Persons
wishing to invoke this exception must appear
before the Board to defend their purposes for
doing so.
(c) Multiple Occupancies
If a building is to house more than one
occupant, each one being individually metered
through a separate set of service conductors,
then each separate occupant space shall have a
single separate current limiting service
disconnecting means outside the building. Each
disconnect is to be housed in its own
2.
enclosure, with its own independent handle
outside of its enclosure. Each meter shall be
considered as a separate occupant.
(d) Article 230-71, National Electrical Code, 1993
Edition, is hereby amended by deleting paragraph
(a) and substituting the following:
(a) General -Maximum Number of Disconnects
(Six Hand Rule)
The service disconnecting means for each
building permitted by Section 230-2 as amended
herein shall consist of not more than six (6)
disconnecting means. If there are to be more
than six (6) occupants in a building,
provisions must be made not to exceed six (6)
disconnecting means outside that building in
order that the building may be completely de -
energized in six (6) throws or less. In
buildings planned to house more than six (6)
occupants, this rule shall be adhered to by
installing a single service disconnect on the
source side of the multiple meters. (Note:
Speculative buildings built to house an
unknown number of occupants will be considered
as being planned to house more than six.)
(e) Article 240-24, National Electrical Code, 1993
Edition, is hereby amended by adding paragraph (e)
which shall read as follows:
(f)
(e) Location of Panel Boards or Overcurrent
Devices
Panel boards or overcurrent devices shall not
be located in bathrooms or within six (6) feet
of sinks, lavatories or similar fixtures.
Panel boards will have the following minimum
clearances: Six (6) feet three (3) inches of
headroom; three (3) feet of walk-up clearance
and thirty (30) inches minimum horizontal
clearance with a minimum of six (6) inches on
each side of enclosure.
Article 300, National Electrical Code, 1993
Edition, is hereby amended by adding Section 23
which shall read as follows:
300-23. Special Safety Measures
(a) Except upon written permission of the building
official, no electrical conductor of any
nature shall be installed nearer than three
(3) inches to any metal pipe or duct which
could operate at temperature in excess of one
3.
(g)
(j)
hundred twenty (120) degrees fahrenheit.
(b) Thermostat, low voltage control wiring and
communications cables in dwellings shall be
protected from mechanical damage and shall
maintain two (2) inches clearance from all
other wiring and pipes. Thermostat, low
voltage control wiring and communications
cables shall be well strapped or supported
with insulated staples or supports not to
exceed four (4) feet spacing.
Article 348, National Electrical Code, 1993
Edition, is hereby amended by adding Section (3)
which shall read as follows:
348-1-(3) Electrical Metal Tubing
Electrical metallic tubing shall not be permitted
for direct burial in earth or installed in or under
concrete on grade or below grade.
Article 300-4, National Electrical Code, 1993
Edition, is hereby amended by deleting subparagraph
(d) thereof.
Article 424-19, National Electrical Code, 1993
Edition, is hereby amended by deleting the first
sentence and substituting the following:
424-19 Disconnecting Means
An approved disconnecting means shall be required
on all fixed electric space heating equipment, the
disconnecting means shall be mounted adjacent to
(not a part of) the equipment, and within sight.
Where heating equipment is supplied by more than
one source; the disconnecting means shall be
grouped and identified.
Article 604, National Electrical Code, 1993
Edition, is hereby amended by adding Section 8
which shall read as follows:
604-8 Color Code (Manufactured Wiring Systems)
All manufactured wiring systems shall be color
coded according to Subsection 3.910(6)(d) of the
City of Round Rock Electrical Code.
(k) Article 605, National Electrical Code, 1993
Edition, is hereby amended by adding Section 9
which shall read as follows:
605-9 Color Code (Office Furnishing Partition
Systems)
4.
All office furnishing partition systems shall have
their internal wiring systems color coded according
to Subsection 3.910(6)(d) of the City of Round Rock
Electrical Code.
III.
The Chapter 3, Section 3.905(1), Code of Ordinances (1990
Edition), City of Round Rock is hereby amended to read as follows:
(1) The examination and license fees for the various classes
of electricians shall be as follows:
Classification Exam Original
of Electrician Fee License Renewal
Master Electrician $35.00 $150.00 $75.00
Journeyman Electrician $35.00 $ 35.00 $25.00
Journeyman $35.00 $ 25.00 $15.00
Restricted
Apprentice $ 10.00 $10.00
IV.
The Chapter 3, Section 3.905(8), Code of Ordinances (1990
Edition), City of Round Rock is hereby repealed.
(8) (Repealed)
V.
The Chapter 3, Section 3.906(9), Code of Ordinances (1990
Edition), City of Round Rock is hereby amended to read as follows:
(9) Issuance of Electrical License
(a) Upon receipt of proof of payment of the required
fee, and passing the examination, the Chief
Electrical Inspector shall issue to the applicant
the class of license which said applicant is
qualified to receive under the provisions of this
Code. The Chief Electrical Inspector shall record
the issuance of said license.
(b) Each license shall bear a distinguishing number
assigned to the licensee, the full name, sex, date
of birth, weight, height, hair color, eye color,
and a space upon which the licensee shall write
5.
his/her usual signature in permanent ink
immediately upon receipt of the license. No
license shall be valid until it is so signed by the
licensee.
VI.
The Chapter 3, Section 3.906(12), Code of Ordinances (1990
Edition), City of Round Rock is hereby repealed.
(12) (Repealed)
VII.
A. All ordinances, parts of ordinances, or resolutions in
conflict herewith are expressly repealed.
B. The invalidity of any section or provision of this
ordinance shall not invalidate other sections or provisions
thereof.
Alternative 1.
By motion duly made, seconded and passed with an affirmative
vote of all the Council members present, the requirement for
reading this ordinance on two separate days was dispensed with.
READ, PASSED, and ADOPTED on first reading this `-62) day
of TY1O,1t , 1993.
Alternative 2.
READ and APPROVED on first reading this the day of
, 1993.
READ, APPROVED and ADOPTED on second reading this the
day of , 1993.
/71
MIKE ROBINSON, Mayor
City of Round Rock, Texas
6.
ATTEST:
JONE LAND, City Secretary
7.
05/11/93 15:.36 ROUND ROCK PUELIC WORKS 512 255 6676
DATE: May 11, 1993
. NO.460 P07
SUBJECT: City Council Meeting, May 13, 1993
ITEM: 11D. Consider an ordinance to update the National Electrical Code.
(First reading)
STAFF RESOURCE PERSON: Jim Nuse
STAFF RECOMMENDATION:
The Round Rock Electrical Review Board has recommended to update the National
Electric Code. Adoption of this ordinance will bring the 1993 NEC into effect. Jerry Wanslow,
Chief Electrical Inspector, will make a presentation.