O-87-2314 - 12/22/1987ORDINANCE NO. _ a_
AN ORDINANCE AMENDING CHAPTER 3, SECTION 8, CODE OF ORDINANCES,
CITY OF ROUND ROCK, TEXAS; ADOPTING THE NATIONAL ELECTRIC CODE,
1987 EDITION, WITH AMENDMENTS; AMENDING DEFINITIONS OF BUILDING
AND FIREWALL; AMENDING REQUIREMENTS FOR INSPECTIONS; AMENDING
COMPOSITION OF ELECTRICAL EXAMINING AND ADVISORY BOARD; AMENDING
THE REQUIREMENTS FOR EXAMINATION AND EXAMINATION FEES FOR
ELECTRICIANS; AMENDING THE REQUIREMENTS FOR APPLICATIONS FOR
PERMITS; AMENDING CERTAIN SAFETY STANDARDS FOR METERS AND METER
LOOPS, ELECTRICAL CIRCUITS, DWELLING CIRCUITS, AND COMMERCIAL
BUILDINGS; PROVIDING A SAVINGS CLAUSE AND REPEALING CONFLICTING
ORDINANCES.
BE IT ORDAINED BY THE COUNCIL OF THE CITY OF ROUND ROCK, TEXAS.
I.
That Chapter 3, Section 8, A, Code of Ordinances, City of Round
Rock, Texas, is hereby amended by deleting paragraph (2) and
substituting the following:
(2) NATIONAL CODE
The National Electrical Code, 1987 Edition, as
amended herein, is hereby adopted as part of this
Code to the same effect as if it were copied
verbatim herein and shall be in effect except as
it may be in conflict with the provisions of this
section. It may be referred to herein as NEC.
II.
That Chapter 3, Section 8, A., Code of Ordinances, City of Round
Rock, Texas, is hereby amended by adding a paragraph (8) which shall
read as follows:
(8)
AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1987
EDITION
(a) Article 210-8(a), National Electrical Code,
1987 Edition, is hereby amended by adding
sub -paragraph (7) which shall read as
follows:
(7) All receptacles protected by one or more
ground -fault circuit interceptors devices
shall be identified.
(b) Article 210-70, National Electrical Code,
1987 Edition, is hereby amended by adding
paragraph (c) which shall read as follows:
(c) Other Requirements
Convenience outlet and lighting outlet will
be required in all attic space or under floor
spaces where equipment needing servicing is
located. These outlets must be within six (6)
feet of this equipment.
C19ORDINCP3
(c) Article 220, National Electrical Code, 1987
Edition, is hereby amended by deleting
Section 22 and substituting the following:
220-22. Neutral Conductor
Neutral conductors shall be of the same
ampacity as the largest ungrounded conductor.
(d) Article 230, National Electric Code, 1987
Edition, is hereby amended by deleting
Section 2 and substituting the following:
230-2. Services
(a) Number of Services; Single Occupancy.
If a building is to house only one single
occupant then a single service disconnect
shall be installed outside the building.
Exception No. 1: Service Entrance Capacity of
1000 Amps or More
If a building is to house only one single
occupant, has a total service entrance
capacity of 1000 amps or more, and
arrangements have been made with the power
supplier for the installation of a three
phase padmounted transformer, then multiple
service disconnecting means may be installed,
with special permission from the Electrical
Board, at one location outside the building,
up to a maximum number of six (6).
Furthermore, the service disconnecting means
may be installed inside the building on the
ground floor. In this case, the disconnects
shall be located no more than 24 inches from
the point of entrance of the Service Entrance
Conductors, direct access shall be provided
within ten (10) feet of the disconnects from
outside the building, and doors leading to
the disconnects shall be secured by only a
padlock and hasp. Persons wishing to invoke
this exception must appear before the Board
to defend their purposes for doing so.
(b) Number of Services, Multiple Occupancies.
If a building is to house more than one
occupant, each one being individually metered
through a separate set of service entrance
conductors, then each shall have a single
separate service disconnecting means outside
the building. Furthermore, each disconnect is
to be housed. in its own enclosure, with its
own independent handle outside of its
enclosure. (Note: a house meter is considered
to be a separate occupant.)
Any building which houses multiple
occupancies shall have all mains and meters
in conformity with Article 230-71 as amended
herein, and grouped in a common location on
the outside of the building; and they shall
be permanently marked or labeled for each
occupancy.
2.
(c) Provisions for Locks and/or Seals
All disconnects, panelboards, junction boxes,
troughs and/or secondary enclosures installed
on the source side of the power supplier's
metering equipment shall have a hinged or
slip -fit front covering enclosing all
connections, with provisions for a lock or
seal on the cabinet. Also, no fuses or
circuit breakers are to be used in these
devices.
Exception No. 1: Circuit Breakers will be
allowed if the device has provisions for
resetting a tripped breaker without the
necessity of opening the cabinet and exposing
the connections.
(d) Fire Pumps and other Emergency Equipment
All exceptions outlined in the National
Electric Code referring to fire pumps,
emergency lighting, or other emergency
equipment shall remain valid throughout
paragraphs (a) through (d) above.
Article 230, National Electrical Code, 1987
Edition, is hereby amended by deleting
Section 7 and substituting the following:
230-7. Service Raceway
Conductors other than service conductors
shall not be installed in the same service
raceway or service -entrance cable.
(a) Fused and unfused conductors shall not be
installed in a common raceway.
(b) Metered and unmetered conductors shall
not be installed in a common raceway.
Article 230-24, National Electrical Code,
1987 Edition, is hereby amended by deleting
paragraph (b) and substituting the following:
(b) Clearances
Overhead service drop conductors must have
minimum ground clearances as required by the
National Electrical Code and the National
Electrical Safety Code. In order to maintain
these ground clearances, the attachment
heights for service racks or masts at the
electric service entrance to buildings shall
be provided as outlined in the "Electric
Service Guidelines" handbook published by TU
Electric.
Article 230, National Electrical Code, 1987
Edition, is hereby amended by deleting
Section 43 and substituting the following:
230-43. Wiring Methods
Service -entrance conductors shall be
installed in accordance with the applicable
requirements of this Code covering the type
of wiring method used and limited to the
3.
following methods: (1) rigid metal conduit;
(2) intermediate metal conduit; (3)
electrical metallic tubing; (4) wireways; (5)
busways; (6) auxiliary gutters; (7) rigid
nonmetallic conduit; or (8) cablebus.
service -entrance conductors shall not enter a
building or structure ahead of the
overcurrent protection unless in threaded
type raceway or busway.
(h) Article 230-70, National Electrical Code,
1987 Edition, is hereby amended by deleting
paragraph (b) and substituting the following:
(b) General - Marking disconnecting means
Each service disconnecting means shall be
permanently marked to identify it as a
service disconnecting means by using either a
service address or designer's building -space
designation.
Article 230-71, National Electrical Code,
1987 Edition, is hereby amended by deleting
paragraph (a) and substituting the following:
(a) General -Maximum Number of Disconnects
(Six Hand Rule)
The service disconnnecting means for each
building permitted by section 230-2 as
amended herein shall consist of not more than
six (6) switches. If there are to be more
than six occupants in a building, provisions
must be made not to exceed six (6)
disconnecting means outside that building in
order that the building may be completely
de -energized in six throws or less. In
buildings planned to house more than six
occupants, this rule shall be adhered to by
installing a single main disconnect on the
source side of the multiple meters. (Note:
Speculative buildings built to house an
unknown number of occupants will be
considered as being planned to house more
than six.)
Article 240-24, National Electrical Code,
1987 Edition, is hereby amended by adding
paragraph (e) which shall read as follows:
(e) Location of Panelboards or Overcurrent
Devices
(1)
(j)
Panelboards or overcurrent devices shall not
be located in bathrooms or within six (6)
feet of sinks, lavatories, or similar
fixtures. Panelboards will have the following
minimum clearances: Six feet three inches
(6'3") of headroom; three feet (3') of walk
up clearance and 30 inches minimum horizontal
clearance with a minimum of six inches (6")
on each side of enclosure.
(k) Article 250-42(f), National Electrical Code,
1987 Edition, is hereby amended by deleting
Exception No. 4 and substituting the
following:
4.
Exception No. 4: Listed information
processing equipment protected by a system of
double insulation, or its equivalent, shall
not be required to be grounded. Where such a
system is employed, the equipment shall be
distinctively marked.
(1) Article 300-3, National Electrical Code, 1987
Edition, is hereby amended by deleting
paragraph (a) and substituting the following:
(a) Single Conductors
Single conductors specified in Table 310-13
of the National Electrical Code shall only be
permitted to be installed where part of a
recognized wiring method of Article 300-23 as
amended herein.
(m) Article 300, National Electrical Code, 1987
Edition, is hereby amended by adding Section
23 which shall read as follows:
300-23. Special Safety Measures
(a) All wiring used exclusively for, and
which is within a building or a part of a
building used exclusively as a dwelling,
shall be wired with the equivalent of one of
the following types of approved wiring, all
as regulated by this chapter:
Standard rigid steel or aluminum conduit
Thin wall conduit
Flexible metal raceway
Surface metal raceway
Nonmetallic raceway
Nonmetallic cable (incl. Romex)
(b) Apartment houses having three (3) stories
or less and rooming houses, boarding houses,
fraternity houses and sorority houses having
not more than one (1) story may be wired as
required in subsection (a) of this section;
otherwise, they shall be wired as required in
subsection (c) of this section.
(c) All electrical work in buildings and all
electrical work not included in the two
preceding subsections shall be installed with
the equivalent of one of the following
approved methods:
Standard rigid steel or aluminum conduit
Thin wall conduit
Surface metal raceways
Nonmetallic raceways
Flexible metallic conduit
(Flexible metallic conduits shall
not be enclosed in plaster or
masonry)
(d) Equipment wired with other methods and
which bear Underwriter's Laboratory, Inc.,
label of approval, and which have been
approved by the Electrical Board shall
constitute exceptions.
5.
(e) Non -weatherproof electrical materials
will be considered as not exposed to weather
if run on the ceiling twelve (12) inches or
more from outside edge of roofs or awnings or
on side walls more than forty-five degrees
(45 ) inside from a vertical line at outside
edge of roof.
(f) Unfused service conductors shall be
connected to the meter box by fastening the
unfused service conductor on the exterior of
the building or structure. No unfused service
conductor (service entrance cable) shall be
permitted in the walls or inside the
structure of any single-family or multifamily
dwelling three (3) stories or less.
(g) All lighting outlets within reach of a
grounded surface shall be controlled by a
wall switch.
(h) Except upon written permission of the
Building Official, no electrical conductor of
any nature shall be installed nearer than
three (3) inches to any metal pipe or duct
which could operate at temperature in excess
of one hundred twenty degrees fahrenheit
(120 F.) .
(i) Any switch that can be reached from a tub
enclosure or shower enclosure will be of the
grounded type and have nylon or plastic plate
crews and plate cover with no exposed metal
parts.
(j) Galvanized tie wire shall not be
permitted for strapping in any form.
(k) Thermostat, low voltage control wiring
and communications cables in dwellings shall
be protected from mechanical damage and shall
maintain two (2) inches clearance from all
other wiring and pipes. thermostat, low
voltage control wiring and communications
cables shall be well strapped or supported
with insulated staples, supports not to
exceed four (4) feet spacing.
(n) Article 310, National Electrical Code, 1987
Edition, is hereby amended by adding the
following language to the footnotes to Table
310-16.
NOTE: Conductor Ampacity
Ampacities of insulated conductors listed in
the 85° C. and 90° C. columns shall be that
listed in the 75° C. column. (Most
terminations are designed only for 60°C. or
75° C. minimum temperatures; therfore, the
higher rated ampacities for conductors of 90°
C., 110° C., etc., cannot be utilized unless
the terminations have comparable ratings.).
(o) Article 339-1, National Electrical Code, 1987
Edition, is hereby amended by deleting
paragraph (a) and substituting the following:
6.
(p)
(q)
(a) Description
Underground feeder and branch circuit cable
shall be a approved type of cable in sizes
#12 copper through #10 copper. The conductor
of type UF shall be one of the moisture
resistant type listed in Table 310-13 which
is suitable for branch circuit wiring.
Article 339-3
1987 Edition,
sub -paragraph
following:
(a), National Electrical Code,
is hereby amended by deleting
(1) and substituting the
(a) Uses Permitted
(1) Type UF cable shall be permitted for
use underground, including direct burial
in the earth, on residential branch
circuits less than 150 volts to ground,
30 amperes or less, where provided with
overcurrent protection of the rated
ampacity as required in Section 339-4 of
the National Electrical Code.
Article 348, National Electrical Code, 1987
Edition, is hereby amended by adding Section
(3) which shall read as follows:
348-3 Electrical Metal Tubing
Electrical metallic tubing shall not be
permitted for direct burial in earth or
installed in or under concrete on grade or
below grade.
(r) Article 424-19, National Electrical Code,
1987 Edition, is hereby amended by deleting
the first sentence and substituting the
following:
424-19 Disconnecting Means
An approved disconnecting means shall be
required on all fixed electric space heating
equipment, the disconnecting means shall be
mounted adjacent to (not a part of) the
equipment, and within sight. Where heating
equipment is supplied by more than one
source; the disconnecting means shall be
grouped and identified.
In addition, within the area around fixed
electric space heating units in attics, crawl
spaces or mechanical rooms, adequate lighting
shall be installed with a switch for service
of equipment, and a convenience outlet shall
be installed within six (6) feet of
equipment. Both lighting and convenience
outlets are to be installed on the service
access side of the heating units.
(s) Article 600-6, National Electrical Code, 1987
Edition, is hereby amended by adding
paragraph (d) which shall reads as follows:
(d) Outside Signs.
All lighting classified as signs, and
which is installed outside the main walls
of any building, shall be on approved
circuits supplying no load within the
7.
building. Also, all signs must have a
disconnecting means provided outside the
building, on the sign itself, or within 50
feet of the sign.
(t) Article 604,
Edition, is
8 which shall
(w)
604-8 Color
Systems)
National Electrical Code, 1987
hereby amended by adding Section
read as follows:
Code (Manufactured Wiring
All manufactured wiring systems shall be
color coded according to subsection G.9.c of
the City of Round Rock Electrical Code.
Article 605, National Electrical Code, 1987
Edition, is hereby amended by adding Section
9 which shall read as follows:
605-9 Color Code (Office Furnishing Partition
Systems)
All office furnishing partition systems shall
have their internal wiring systems color
coded according to subsection G.9.c of the
City of Round Rock Electrical Code.
III.
That Chapter 3, Section 8, C.(4), Coded Ordinances, City of
Round Rock, Texas, is hereby amended by adding a sub -paragraph (k)
which shall read as follows.
(k) No service entrance equipment shall be connected
to an electrical distribution system unless it
has been approved and a permit shall have been
obtained and fees paid. (Note: this shall include
all industrial and commercial tenant or occupant
changes within existing buildings.)
IV.
That Chapter 3, Section 8, B., Code of Ordinances, City of Round
Rock, Texas, is hereby amended by deleting paragraph (13) and
substituting the following:
(13) BUILDING:
A structure which stands alone or which is cut
off from adjoining structures and/or occupancies
by one or more fire walls.
V.
That Chapter 3, Section 8, B., Code of Ordinances, City of Round
Rock, Texas, is hereby amended by adding a paragraph (14) which shall
read as follows:
8.
(14) FIRE WALL:
A single wall that stands between two (2) or more
building occupancies having a minimum fire
withstand rating of four (4) hours, as outlined
by the City's Building Code, and having no
penetrations by plumbing, electrical or
communications equipment, fixtures, conduits,
raceways, or passageways.
VI.
That Chapter 3, Section 8, C.(5), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by substituting "Texas Utilities
Electric Company (TU Electric)" for "Texas Power & Light Co. (TP&L)"
in the first sentence.
VII.
That Chapter 3, Section 8, C.(5), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by deleting sub -paragraph
and substituting the following:
(m)
The Electrical Board of the City of Round Rock
may waive the requirement for an examination to
electricians with licences from cities which
agree to reciprocate with the City of Round Rock.
Such waiver may be granted if the examination
taken by the applicant is similar to the
examination given by the City. With the Board's
acceptance, the examination and examination fees
may be waived.
VIII.
(m)
That Chapter 3, Section 8, D.(1), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by deleting sub -paragraph (b).
IX.
That Chapter 3, Section 8, D., Code of Ordinances, City of Round
Rock, Texas, is hereby amended by deleting paragraph (3) and
substituting the following:
(3)
APPLICATION GENERALLY:
Application for permits shall be made in writing
upon forms provided by the City for the purpose.
The application shall contain the following
information: the date the application is
submitted, the name of the person under whose
authority the application is made, the name of
the person actually offering the application, the
address where electrical work is to be done, a
description of the electrical work to be done and
other pertinent information required by the Chief
Electrical Inspector.
9.
(a) When required by the Chief Electrical
inspector, the application shall include a
diagram or plan showing clearly the following:
(i) The character and kind of wiring or
installation of fixtures or equipment work to
be done.
(ii) The plan or electrical diagram shall
have a definite scale and show the manner in
which the electrical installation is to be
made.
(iii) The character of any repairs to any
existing installation showing the point at
which service connection is required.
(iv) The site of the feeders and sub -feeders.
(v) The location at service switches and
centers of distribution.
(vi) The arrangement of circuits and the
number of outlets connected thereto.
(vii) Load Calculations.
(viii) A profile view of the service entrance
equipment including all gutter troughs,
junction boxes, switches, disconnects, fuses,
panel boards, current transformer enclosures
and meter sockets, showing how this equipment
is to be arranged on the wall of the
building.
(ix) The maximum available fault current at
the service entrance.
(x) Fault current bracing information.
X.
That Chapter 3, Section 8, D(4), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by deleting sub -paragraphs (a),
(b) and (c) and substituting the following:
(a) Permits shall be issued to licensed Master
Electricians, or their duly authorized agents, who
shall be certified to the Chief Electrical Inspector
by affidavit stating that said electrician assumes all
and full responsibility for any permit taken out or
applied for by said agent.
(b) The City of Round Rock operates under a "One Permit"
system whereby a General Contractor or Owner may
secure a single permit covering all of the building,
electrical, plumbing, heating, ventilating and air
conditioning requirements. Therefore, electrical work
may be performed under this "One Permit" system.
However, on the special occasions where only
electrical work is being performed, a Master
Electrician, as defined herein, must secure a permit
covering the work to be done.
(c) When the permitted electrician fails or refuses to
complete electrical work, in whole or in part, on any
electrical wiring or installation of fixtures or
10.
equipment, a new permit may be issued upon written
request of the owner or person in charge of
construction, and fees therefore shall be assessed
covering all electrical work done or to be done,
whether completed or not at the time a subsequent
permit is issued. Before any subsequent permit is
issued, the enforcement official shall notify the
permitted electrician failing or refusing to complete
the electrical work, if he can be found, to show cause
within ten days of receipt of written notice why a
subsequent permit should not be issued to a subsequent
electrician. All written requests for subsequent
permits shall set forth the reasons why the current
permitted electrician has failed or refused to
complete electrical work. If subsequent permits are
issued, all existing permits shall be cancelled by the
enforcement official.
XI.
That Chapter 3, Section 8, G.(2), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by deleting sub -paragraphs (c)
and (d) and NOTE following sub -paragraph (d).
XII.
That Chapter 3, Section 8, G.(5), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by deleting sub -paragraph (a)
and substituting the following:
(a) All circuits shall have conductors sized in
accordance with Article 310 of the National
Electrical Code. No conductor smaller than No. 12
Copper American Wire Gauge size, or equivalent,
shall be used in any electrical work as covered
by this chapter, except the following as approved
by the National Electrical Code:
Pendant and portable cords.
No. 14 for control circuits, operating
contactors, relays, and the like.
Wiring within display cases.
Wiring for system covered by Chapter 7 of the
National Electrical Code.
As specified under electrical signs.
XIII.
That Chapter 3, Section 8, G.(5), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by adding sub -paragraphs (i),
(j)
and (k) which shall read as follows:
(i) Plastic anchors will not be accepted as a
mounting means on cinder block, brick, concrete,
rock, plaster or any material that falls within
these descriptions.
11.
(j) There shall be no PVC extended above the floor
line in any exposed work.
(k) "Lay -in" type lighting fixtures will only be
allowed to have a minimum of six (6) feet of flex
tail.
XIV.
That Chapter 3, Section 8, G.(7), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by adding sub -paragraph (h)
which shall read as follows:
(h) Two or more metered service drops being fed by
different voltages and/or phase configurations
will not be permitted.
XV.
That Chapter 3, Section 8, G.(8), Code of Ordinances, City of
Round Rock, Texas, is hereby amended by deleting sub -paragraphs (a)
and (b) and substituting the following:
(a) The kitchen for each dwelling shall have no less
than two (2) twenty amperes circuits which shall
comply with NEC Article 210, except that there
shall be a maximum of three (3) outlets per
circuit. Dedicated circuits such as refrigerator,
disposal, microwave, washing machine, furnace,
bathroom heater and dishwasher shall be on
separate circuits and not be counted as any of
the circuits required for every new or remodeled
dwelling.
(b) In areas other than kitchens in dwelling units no
more than nine (9) outlets shall be connected to
any circuit, whether the outlets be ceiling or
wall outlets (receptacle outlet or lighting
fixture outlets), and no single cirucits shall
supply an area of 300 square feet or more.
XVI.
A. All ordinances, parts of ordinances, or resolutions in conflict
herewith are expressly repealed.
B. The invalidity of any section or provision of this ordinance
shall not invalidate other sections or provisions thereof.
READ AND APPROVED on first reading this /0 th day of awynlAefu
1987. �?
READ, APPROVED, AND ADOPTED on second reading this A/1 day
of , 1987.
ATTEST:
'iz 4/z/1.
MIKE ROBINSON, Mayor
City of Round Rock, Texas
J NNE LAND Ci Secretary y
DATE: December 17, 1987
SUBJECT: Council Agenda, December 22, 1987
ITEM: 7A. Consider an ordinance revising the Electrical Code.
(Second Reading)
STAFF RESOURCE PERSON: Jim Nuse
STAFF RECOMMENDATION: Passage on the second reading of the ordinance.
ECONOMIC IMPACT: This is the second reading of the Electrical Code
revisions. This item has been a previous work session
item. This Code updates licensing procedures as well
as material and installation procedures. Although
there is no direct economic indicator for this item,
it is reasonable to believe that complete and equitable
codes will most wisely use the builders resourses.